Air velocity affects three different parts of an extraction system: capture at the source, transport through ductwork and flow through the filter medium. Treating these as one universal velocity leads to poor design because each has a different purpose.
Capture velocity
The hood must create enough air movement at the emission point to overcome the contaminant’s release momentum and local cross-draughts. Required capture depends on hood geometry, distance, thermal buoyancy and process movement. Moving a hood closer is often more efficient than increasing total airflow.
Transport velocity in ductwork
Duct velocity keeps dust or material suspended until it reaches the separator. If it is too low, deposits form in horizontal runs and branches. If it is unnecessarily high, pressure loss, noise, abrasion and energy use increase. The suitable range depends on particle size, density, loading and duct geometry.
Velocity through filtration media
Filter face or media loading relates the airflow to the effective filtration area. Excessive loading increases pressure drop and can shorten filter life. A larger filter area generally lowers media velocity, but cleaning method, dust behaviour and equipment size also matter.
How velocity affects lifecycle
- low capture velocity allows pollutants to escape;
- low transport velocity encourages duct deposits;
- excessive duct velocity accelerates wear and fan energy demand;
- excessive filter loading causes rapid pressure increase;
- unbalanced branches create both high- and low-velocity problems in the same network.
Why generic recommended values are insufficient
Wood chips, fine welding fume, abrasive dust and oil mist cannot use the same design assumptions. Published ranges are a starting point, but final values follow the contaminant, hood, process and equipment data. Pressure-loss calculations then determine the fan duty.
Measurement and control
Commissioning records airflow or pressure at representative branches, duct velocity where required, filter pressure drop and fan operating data. Later measurements reveal loading, leaks, deposits or gate faults. Variable-speed control can adapt demand, provided minimum transport and safety requirements remain satisfied.
Ask ALWO to evaluate capture, duct and filtration velocities for a new system or a network that has lost performance.