Produse ATDG Model Low to Medium Pressure Fans
The ATDG model centrifugal fans are designed for low to medium-pressure applications, specifically for clean air suction at a maximum inlet air temperature of 60°C. These fans are constructed from galvanized steel sheet (painted upon request) and include a dynamically and statically balanced metal rotor. They can be customized upon request for various needs, such as spark-resistant versions with non-ferrous lining and EX-proof motors, anti-corrosion versions made from stainless steel, or high-temperature-resistant versions with a special shaft and cooling impeller.
Model | Installed Power (kW) | Rotation Speed (rpm) | Minimum Flow Rate (m³/h) | Maximum Flow Rate (m³/h) | Flow Rate (m³/h) | Pressure (mm H₂O Column) |
ATDG 400 | 0,75 | 1385 | 2100 | 4900 | 2100 | 53 |
2800 | 48 | |||||
3500 | 43 | |||||
4200 | 38 | |||||
4900 | 34 | |||||
ATDG 450 | 1,1 | 1390 | 3500 | 7000 | 3500 | 62 |
4500 | 56 | |||||
5500 | 50 | |||||
6000 | 47 | |||||
7000 | 42 | |||||
ATDG 500 | 2,2 | 1420 | 4900 | 9800 | 4900 | 90 |
6300 | 80 | |||||
7000 | 71 | |||||
8400 | 66 | |||||
9800 | 58 | |||||
ATDG 535 | 3 | 1420 | 5950 | 11900 | 5950 | 100 |
7650 | 90 | |||||
9350 | 80 | |||||
10200 | 76 | |||||
11900 | 67 | |||||
ATDG 560 | 4 | 1425 | 7000 | 14000 | 7000 | 115 |
9000 | 103 | |||||
11000 | 91 | |||||
13000 | 80 | |||||
14000 | 75 | |||||
ATDG 600 | 5,5 | 1425 | 8750 | 17500 | 8750 | 137 |
11250 | 122 | |||||
13750 | 108 | |||||
15000 | 101 | |||||
17500 | 88 | |||||
ATDG 670 | 11 | 1465 | 10800 | 24000 | 10800 | 174 |
13500 | 170 | |||||
16800 | 161 | |||||
21300 | 141 | |||||
24000 | 122 | |||||
ATDG 710 | 15 | 1465 | 14000 | 28000 | 14000 | 190 |
18000 | 170 | |||||
22000 | 140 | |||||
26000 | 120 | |||||
28000 | 110 | |||||
ATDG 800 | 22 | 1465 | 21000 | 42000 | 21000 | 252 |
27000 | 215 | |||||
33000 | 181 | |||||
39000 | 149 | |||||
42000 | 135 | |||||
ATDG 900/T | 45 | 1470 | 28000 | 56000 | 28000 | 335 |
36000 | 293 | |||||
44000 | 252 | |||||
52000 | 215 | |||||
56000 | 197 | |||||
ATDG 1120/T | 37 | 975 | 34000 | 74000 | 34000 | 225 |
43000 | 200 | |||||
53000 | 170 | |||||
66000 | 144 | |||||
74000 | 132 | |||||
ATDG 1250/T | 75 | 980 | 47000 | 100000 | 47000 | 285 |
59000 | 250 | |||||
74000 | 220 | |||||
85000 | 195 | |||||
100000 | 165 | |||||
ATDG 1400/T | 110 | 985 | 66000 | 140000 | 66000 | 355 |
85000 | 320 | |||||
100000 | 285 | |||||
120000 | 245 | |||||
140000 | 205 |